VEGAMET 381

Category
Manufacturer
Request a price
    Description

    Signal conditioning and display instrument for level sensors

    Displays the measured values and gives simple control functions


    Application area


    Designed to be used in a variety of industries. The VEGAMET 381 is ideal for simple control tasks. The controller powers the connected 4 … 20 mA/HART sensor, processes and displays the measured values . Comprehensive adjustment functions enable individual adaptations to the respective application. 


    Benefits


    ●    Highly readable LC display through digital and quasi analogue indication of the measured value
    ●    Transmitter power supply via the 4 … 20 mA sensor input
    ●    Flexible use through two relay outputs to control pumps and stirrers, etc.

     

     

     

    Technical data

    Series Instrument for mounting into front panel, switching cabinet or housing

    Connection terminals

    • Type of terminal Screw terminal
    • Max. wire cross-section 1.5 mm² (AWG 16)

    Operating voltage 20 … 253 V AC, 50/60 Hz, 20 … 253 V DC

    Max. power consumption 12 VA, 4 W

    Sensor input

    Number of sensors 1 x 4 … 20 mA

    • mode active Sensor supply through VEGAMET 381
    • mode passive Sensor has an own power supply

    Deviation Accuracy ±20 µA (0.1 % of 20 mA)

    Relay outputs

    • Quantity 2 x operating relay, 1 x fail safe relay
    • Switching voltage min. 10 mV DC, max. 250 V AC/DC
    • Switching current min. 10 µA DC, max. 3 A AC, 1 A DC
    • Breaking capacity min. 50 mW, max. 500 VA, max. 54 W DC

    Current output

    • Quantity 1 x output
    • Range 0/4 … 20 mA
    • Max. load 500 Ω

    Ambient temperature

    • -20 … +60 °C (-4 … +140 °F)

    Protection rating

    • Wall, rail mounting IP 20
    • Front panel mounting IP 40

    Instruction

    The VEGAMET 381 signal conditioning instrument powers a 4 … 20 mA sensor and processes its measured value. Through an adjustment on VEGAMET this measured value can be scaled individually and outputted to connected instruments via the current output. Beside the large indication there are two operating relays that serve as limit alarms for control tasks.

    VEGAMET 381 is adjusted on the front via a clear LC display and a 16- step function switch as well as two keys.

    Attachment Size
    DocumentDownloadHandler (16).pdf 267.47 KB