VEGAMET 625

Category
Manufacturer
Request a price
    Description

    Signal conditioning and display instrument for level sensors

    Application area

    Measured value indication, simple control functions such as remote enquiry of measured values for two HART sensors

    The VEGAMET 625 controller powers the connected 4 … 20 mA/HART sensor, processes and displays the measured values received through HART Multidrop. The VEGAMET 625 is ideal for simple control tasks in level, gauge and process pressure measurements. For inventory management in remote storage silos, interfaces for simple remote data transmission are integrated. Comprehensive adjustment functions enable individual adaptations to the respective application.

    Your benefit

    • Simple data recording and history retrieval from instruments with digital interface
    • Simple integration into the Intranet/Extranet through integrated Web server
    • Versatile use through three scalable current outputs for control of indications and connected systems such as e.g. a PLC

     

     

    Technical data

    Series Module unit with plug-in socket for mounting on carrier rail (35 x 7.5 according to DIN EN 50022/60715)

    • Type of terminal Screw terminal
    • Max. wire cross-section 1.5 mm² (AWG 16)

    Sensor input

    Number of sensors 2 x VEGA HART sensors

    Type of input (selectable)

    • Active input Sensor supply through VEGAMET 625
    • Passive input Sensor has an own power supply

    Relay outputs

    • Quantity 3 x operating relay, 1 x fail safe relay
    • Switching voltage min. 10 mV DC, max. 250 V AC/DC
    • Switching current min. 10 µA DC, max. 3 A AC, 1 A DC
    • Breaking capacity min. 50 mW, max. 750 VA, max. 40 W DC

    Current outputs

    • Quantity 3 x outputs
    • Range 0/4 … 20 mA, 20 … 0/4 mA
    • Max. load 500 Ω

    Ethernet interface (optional)

    • Quantity 1 x, cannot be combined with RS232
    • Data transmission 10/100 MBit

    Ambient conditions

    • Ambient temperature -20 … +60 °C (-4 … +140 °F)

    Protection rating

    • Instrument IP 30
    • Terminal socket IP 20

    Instruction

    The VEGAMET 625 signal conditioning instrument powers two HART sensors and processes their measured values. Through an adjustment on the VEGAMET, these measured values can be individually scaled/ linearised and transferred to downstream systems via the current outputs. Beside the graphic-capable indication there are three operating relays that serve as limit alarms for control tasks. With instruments with optional interface, measured values can be retrieved via modem or network and indicated with the aid of a web browser or WEB-VV. In addition, it is possible to send a measured value or message via e-mail.

    The adjustment of VEGAMET 625 is menu-driven via four keys in the front and a clear, graphic-capable LC display with background lighting. As an alternative, parameter adjustment of the instrument is also possible via the adjustment software PACTware and the respective DTM.

    Attachment Size
    34767-EN-VEGAMET-625.pdf 454.38 KB
    Request a price