    Signal conditioning instrument for up to 15 HART sensors

    Application area

    Measured value indication and remote enquiry of measured data for up to 15 HART sensors

    The VEGASCAN 693 is a controller and display instrument for up to 15 continuously measuring 4 ... 20 mA/HART sensors. It processes the measured values received via HART multidrop and displays the values. Hence measurement results from level, gauge and process pressure measurements can be easily made available to control systems, visualizations and the remote data transmission. Interfaces and functions for the connection to networks and the remote data transmission are integrated. It is particularly suitable for applications in the local and global inventory management.

    Your benefit

    • Data recording of up to 200,000 measured values ​​for devices with digital interface
    • Simple integration into the Intranet/Extranet through integrated Web server
    • Measured value and message transmission via e-mail and SMS and data transmission to WEB-VV

     

     

    Technical data

    Series Module unit with plug-in socket for mounting on carrier rail (35 x 7.5 according to DIN EN 50022/60715)

    • Type of terminal Screw terminal
    • Max. wire cross-section 1.5 mm² (AWG 16)

    Sensor input

    Number of sensors 15 x VEGA HART sensors (5 x with Ex version)

    Type of input (selectable)

    • Active input Sensor power supply by VEGASCAN
    • Passive input Sensor has an own power supply

    Measured value transmission

    HART multidrop protocol digital for VEGA HART sensors

    Cycle time until the next measured value update max. 5 seconds (depending on the number of connected sensors)

    Fail safe relay

    • Switching voltage min. 10 mV DC, max. 250 V AC/DC
    • Switching current min. 10 µA DC, max. 3 A AC, 1 A DC
    • Breaking capacity min. 50 mW, max. 750 VA, max. 40 W DC

    Ethernet interface (optional)

    • Quantity 1 x, cannot be combined with RS232
    • Data transmission 10/100 MBit

    RS232 interface (optional)

    • Quantity 1 x, cannot be combined with Ethernet

    Ambient conditions

    • Ambient temperature -20 … +60 °C (-4 … +140 °F)

    Protection rating

    • Instrument IP 30
    • Terminal socket IP 20

    Instruction

    The VEGASCAN 693 signal conditioning instrument can power up to 15 HART sensors and process their digital measured values. The measured value transmission is carried out via a bus system (HART multidrop). The requested parameter is shown in the display and can also be outputted to one of the integrated interfaces and the web server. With instruments with optional interface, measured values can be retrieved via modem or network and indicated with the aid of a web browser or WEB-VV. In addition, it is possible to send a measured value or message via e-mail.

    The adjustment of VEGASCAN 693 is menu-driven via four keys in the front and a clear, graphic-capable LC display with background lighting. As an alternative, parameter adjustment of the instrument is also possible via the adjustment software PACTware and the respective DTM.