- Signal conditioning
- Controllers (Vega)
Description
Single channel controller for level detection
Transmission of 8/16 mA signals for level signalling (single channel)
Application area
The VEGATOR 121 is a controller for the vibrating level switches VEGASWING, VEGAVIB and VEGAWAVE.
The devise is for level detection with relay output with electronics version "Two-wire 8/16 mA“.
This instrument is designed for simple control tasks such as overflow or dry run protection.
Optionally a false signal output is available.
Your benefit
Simple installation
Monitoring detects short circuit and open circuit of the measuring line and disturbances in the sensor
Youcan switch over option of the fail safe relay to the second function relay
Simple and comfortable SIL and WHG function test is done by means of test key.
The instrument includes 1 x sensor input two-wire 8/16 mA input, 1 x relay output (SPDT) output, optional 1 x fail safe relay output (SPDT). The instrument supports carrier rail mounting 35 x 7.5 according to EN 50022 and includes optional SIL qualification up to SIL2.
Specifications
Technical data
Series Module unit for mounting on carrier rails 35 x 7.5 acc. to EN 50022/60715
Connection terminals
- Type of terminal Screw terminal
- Max. wire cross-section 2.5 mm² (AWG 12)
Voltage supply
- Operating voltage 20 … 253 V AC/DC, 50/60 Hz
- Max. power consumption 3 W (8 VA)
Sensor input
- Quantity 1 x analogue
- Input type Active (sensor power supply by VEGATOR 121)
- Measured value transmission Analogue 8/16 mA
- Switching threshold Ʋ On 12.1 mA Ʋ Off 11.9 mA Ʋ
- Tolerance ± 500 µA
- Current limitation 23 mA (permanently short-circuit proof)
- Terminal voltage (idle state) 18.2 V DC, ± 5 %
- Internal resistance 200 Ω, ± 1 %
- Detection line break ≤ 3.6 mA
- Detection shortcircuit ≥ 21 mA
Relay output
- Quantity 1 x operating relay, 1 x fail safe relay (optional)
- Contact Floating spdt
- Contact material AgSnO2, hard gold-plated
- Switching voltage min. 10 mV DC, max. 250 V AC/60 V DC
- Switching current min. 10 µA DC, max. 3 A AC, 1 A DC
- Breaking capacity min. 50 mW, max. 500 VA, max. 54 W DC (with U less than 40 V)1)
Ambient conditions
- Ambient temperature at the installation location of the instrument -20 … +60 °C (-4 … +140 °F)
- Storage and transport temperature -40 … +70 °C (-40 … +158 °F)
Electrical protective measures
- Protection rating IP 20
- Overvoltage category II
- Protection class II
Electrical separating measures
Reliable separation according to VDE 0106 part 1 between all circuits
- Reference voltage 253 V
- Isolation resistance 4.2 kV
Instruction
Instruction
All adjustment elements are located under a hinged front plate. The operating mode, switch-on pulse monitoring and the switching delay can be set via a DIL switch block. In addition, the correct function of the measuring system can be checked by simply pressing a key.
The VEGATOR 121 signal conditioning instrument powers connected sensors and simultaneously processes their measuring signals. When the medium reaches the switching point of the sensor, the sensor current changes. This is measured and evaluated by VEGATOR 121. The change causes the output relays to switch according to the set operating mode
Protection of the environment is one of our most important duties. That is why we have introduced an environment management system with the goal of continuously improving company environmental protection. The environment management system is certified according to DIN EN ISO 14001.
This is a state-of-the-art instrument complying with all prevailing regulations and guidelines. The instrument must only be operated in a technically flawless and reliable condition. The operator is responsible for the trouble-free operation of the instrument. During the entire duration of use, the user is obliged to determine the compliance of the necessary occupational safety measures with the current valid rules and regulations and also take note of new regulations. The safety instructions in this operating instructions manual, the national installation standards as well as the valid safety regulations and accident prevention rules must be observed by the user. For safety and warranty reasons, any invasive work on the device beyond that described in the operating instructions manual may be carried out only by personnel authorised by the manufacturer. Arbitrary conversions or modifications are explicitly forbidden. The safety approval markings and safety tips on the device must also be observed.